HOME/KNOWLEDGE BASE/POINT-TYPE DETECTION/SIEMENS CERBERUS PRO OOH740
Point-Type Detection

Siemens Cerberus PRO OOH740

Multi-sensor smoke detector using ASAtechnology signal processing: two optical sensors plus two heat sensors on the C-NET bus.

Multi-sensor detectorOptical + heatC-NET addressableCollective / conventional
OriginSwitzerland (Siemens Switzerland Ltd, Zug)
OwnershipSiemens Smart Infrastructure

Detection behaviour and immunity

The detector is built to shrug off the things that cause nuisance alarms. Siemens lists resistance to dust, fibres, insects, humidity, extreme temperatures, electromagnetic interference, corrosive vapours, vibration, synthetic aerosols and atypical fire phenomena, alongside insensitivity to impact and tamper protection.

Underneath that sits a redundant, high-quality sensor system with sophisticated sensor and electronics surveillance, protected electronics and high immunity to power-electronic disturbance. The alarm indicator is centred in the detector and visible at 360°, so no alignment is needed at install.

  • Signal processing with ASAtechnology: time- and process-dependent detection behaviour
  • Event-controlled detection behaviour, selectable by application-specific ASA parameter sets
  • Redundant sensor system with integrated short-circuit isolator between two detectors
  • Automatic address allocation during commissioning
  • Up to two external alarm indicators connectable per detector
  • Permissible air speed up to 5 m/s

Technical data

OOH740 and OOHC740 compared
ItemOOH740OOHC740
DesignationMulti-sensor smoke detector, ASAFire and CO detector, neural ASA
Part numberS54320-F7-A3S54320-F8-A3
Sensing2 optical + 2 heat2 optical + 2 heat + CO cell
Operating voltage (modulated)DC 12 … 33 VDC 12 … 33 V
Operating current (quiescent)~170 … 250 µA~300 … 380 µA
Operating temperature−25 … +55 °C−10 … +50 °C
Storage temperature−30 … +70 °C−20 … +55 °C
Humidity95% rel.15 … 95% rel.
CommunicationC-NET, collective or conventionalC-NET
External alarm indicators22
Protection categoryIP40 (IP44 with RS720 base seal)IP40 (IP44 with RS720 base seal)
Permissible air speedmax. 5 m/smax. 5 m/s
Weight0.100 kg0.100 kg
ColourWhite, ~RAL 9010White, ~RAL 9010
Standards and approvals
ItemOOH740OOHC740
StandardsCEA 4021, EN 54-5, EN 54-7, EN 54-17:2005CEA 4021, EN 54-5, EN 54-7, EN 54-17:2005, VdS 2806
VdS approvalG211070G211047
LPCB approval126ba/01126ba/02
Marine (MED)59 825-13 HHn/a
Marine (Germanischer Lloyd)20 207-11 HHn/a
System compatibilityC-NET FS720; collective FC10C-NET FS720

ASA parameter sets: tuning the detector to the application

Rather than being a fixed device, the OOH740’s behaviour is chosen with parameter sets (pre-engineered algorithm profiles matched to an application). On the addressed C-NET line the detector offers seven parameter sets; in collective/conventional mode three are available, selected physically via the detector base or a parameter-set resistor. Representative sets:

Parameter setModeTypical use
Standard Plus (PS1)Collective + addressedGeneral-purpose balanced detection for most standard rooms and areas
Suppression (PS5)Collective + addressedReliable triggering for extinguishing/suppression release applications
High Sensitive Fast (PS9)Collective + addressedFastest, most sensitive response for critical areas (e.g. data centres)
Additional sets (addressed)Addressed C-NET onlyFurther profiles for deceptive-phenomena and specific process environments (7 total)

Parameter-set availability and behaviour depend on line type, product version and configuration in the Cerberus tools. In collective mode, sets are chosen via base type (e.g. DB110/DB721D) or resistors PSR720-1 (33 kΩ = PS1) / PSR720-2 (68 kΩ = PS2).

Australian standards & AS 1851 servicing considerations

For Australian fire professionals, point-type smoke and multi-sensor detectors are covered by the AS 7240 series (Australia’s adoption of ISO 7240 / EN 54), notably AS 7240.7 (point smoke detectors) and AS 7240.8 (CO fire detectors, relevant to the OOHC740). System design falls under AS 1670.1 and maintenance under AS 1851. The OOH740’s EN 54-5/7/17 certification generally underpins local acceptance; confirm the current Australian product listing before specifying. Practical AS 1851 servicing notes for the OOH740:

  • Functional testing: test each detector’s smoke and (where used) heat response per schedule; the 360° alarm indicator aids visual confirmation.
  • Contamination & clean/replace: the chamber resists dust ingress, but detectors in dirty areas should be checked and cleaned or exchanged using the DX791/FDUD491 tools for high-level units.
  • Parameter-set verification: confirm the configured parameter set still matches the room’s current use (occupancy, process, suppression), especially after fit-out changes.
  • CO cell life (OOHC740): electrochemical CO cells age; verify the CO channel and plan cell replacement within the manufacturer’s service life.
  • Isolator & indicators: confirm the built-in isolator and any external alarm indicators/sounder bases operate correctly.

Confirm the current edition of each standard and the applicable Australian approval with Siemens or an authorised partner before finalising design or maintenance.

Bases and accessories

  • DB721 (S54319-F11-A1): universal base for all FD720 point detectors, recess or surface supply wiring up to 8 mm
  • DB722 (S54319-F19-A1): universal base with base seal and screwless terminals
  • DB721D (S54319-F15-A1): universal base for the OOH740 in collective mode where BS 5839 Part 1 monitoring is required; remove the diode for addressed mode
  • DB110: standard conventional base for series 110 detectors and the OOH740; selects parameter set 1
  • BA720 (S54319-F20-A1): base attachment for surface-mounted tube up to 20 mm or trunking up to 25 × 15 mm
  • LP720 detector locking device (theft protection); FDBZ291 designation plate; RS720 base seal for IP44
  • DBZ1190-AA micro terminal (max 0.5 mm²) and DBZ1190-AB connection terminal (max 2.5 mm²)

Using a base with a loop contact means the detector line is not interrupted even when no detector is fitted, which matters during construction and detector exchange. Detectors can be turned into the base by hand or with the DX791 detector exchanger and its FDUD491 adapter.

Figures on this page are the manufacturer’s published specifications, taken from the Siemens OOH740 / OOHC740 Cerberus PRO datasheet, document A6V10284161_h_en (Manual FD720, Section 2, edition 03.2013). They are reproduced for reference and are not design, compliance or engineering advice. Siemens notes that data and design are subject to change without notice, so confirm every figure against the current datasheet, and design to the standards that apply in your jurisdiction. Australian installations are designed to AS 1670.1 and serviced to AS 1851.

Further reading

Siemens Cerberus PRO brand deep-dive Aspirating smoke detection: the alternative approach AS 1670 fire detection, warning and intercom

Frequently asked

What does the OOH740 actually sense?

Two optical sensors working on the scattered-light principle (forward and backward scattering), plus two heat sensors. The heat sensors are there to raise immunity to deceptive phenomena rather than to act as the primary detection method. The OOHC740 variant adds a carbon monoxide cell.

What is ASAtechnology?

Siemens’ term for Advanced Signal Analysis: signal processing where detection behaviour is time- and process-dependent rather than a fixed threshold, tuned through application-specific ASA parameter sets. On the OOH740 the parameter set can be selected in software, or in the field by fitting a PSR-1 (33k) or PSR-2 (68k) resistor into a DB110 or DB721D base.

Is the OOH740 the neural ASA model?

Not quite. The datasheet lists the OOH740 as "multi-sensor smoke detector, ASA" and the OOHC740 as "fire and CO detector, neural ASA". The neural designation goes with the CO-sensing OOHC740, which analyses smoke, heat and gas together.

Can one detector cover more than one design case?

Yes. The software can set the head to work as a multi-sensor smoke detector, as a smoke detector, or as a heat detector, so a single part number covers several situations. It also runs addressable on C-NET or in collective / conventional mode.

Does it have a built-in isolator?

Yes, an integrated short-circuit isolator that locates the defective part of the detector bus and isolates between two detectors. There is also a built-in alarm indicator visible through 360°, and up to two external alarm indicators can be connected per detector.

Compare with other brands
VIGILANT 850 Series (Generation 6) Ampac XP95 MultiSensor FireSense IntelliQuad
All point-type detection brands