HOME/KNOWLEDGE BASE/FIRE PROTECTION SYSTEMS/SIEMENS CERBERUS PRO
Fire Protection Systems

Siemens Cerberus PRO

Siemens’ modular fire detection line, known for ASA multi-criteria detection and a global engineered-systems footprint.

Addressable fire panelsModular detectionASA detection techEngineered systems
OriginGermany / Switzerland (Siemens)
OwnershipSiemens Smart Infrastructure

Platform overview

Cerberus PRO is Siemens’ intelligent fire detection platform for small, medium and large buildings — a member of the FS720 product generation and a sibling of the larger Sinteso range. It pairs powerful, modular control panels with a deep portfolio of intelligent detectors, aspirating smoke detection, input/output modules, manual call points, sounders and beacons, extinguishing control and wireless devices, all unified by the C-NET detector bus and the C-WEB networking architecture, and managed through the Cerberus software family.

Three ideas define the platform. First, ASA (Advanced Signal Analysis) — a neural, environment-tuned signal-processing technology that gives high sensitivity with strong immunity to deceptive phenomena (steam, dust, cooking aerosols). Second, C-NET — a robust, flexible two-wire detector bus supporting loop, stub and star (T-tap) topologies, automatic device configuration, and built-in short-circuit isolation. Third, scalable networking — from a standalone single-loop panel up to an EN 54-compliant 64-panel network spanning kilometres of fibre, with a common management layer.

Range at a glance

CategoryCerberus PRO components
Control panelsFC721 (1 loop) · FC722 (2–4 loops) · FC723 modular · FC724 (4–8 loops) · FC726 modular · FT724 fire terminal · (US: FC922/FC924)
Detector busC-NET 2-wire — loop / stub / star, up to 252 elements per loop, 40 T-taps, 3.3 km
Detection techASA — Advanced Signal Analysis (neural, environment-tuned parameter sets)
Point detectorsOP720 smoke · OH720 multi-sensor · OOH740 ASA neural · OOHC740 ASA neural fire/CO · HI720 / HI722 heat
Special detectionFDL241-9 linear beam · FDF241-9 flame · ASD & ASD+ aspirating
Aspirating (ASD)FDA221 / FDA241 (standalone, up to 500 / 800 m²)
Aspirating (ASD+)FDA261 / FDA262 (C-NET/FDnet or standalone, up to 6,700 m² per device)
ModulesFDCI222 input · FDCIO222 / FDCIO224 input-output · transponders · line isolators / Ex line adapter
Manual call pointsFDM221 · FDM223 (Ex) · FDM224
Audible / visualFDS221 / FDS224 sounders · FDS227 voice-sounder beacon · DBS720 sounder base · FDSB226 sounder-beacon base
NetworkingC-WEB/SAFEDLINK cluster (≤32 panels) + C-WEB/LAN fibre backbone (≤64 panels)
ExtinguishingFC723 / FC726 + XC10 / XCA2005 kits, XT2001 terminal (EN 12094-1)
WirelessSWING — FDOOT271 detector · FDM275 call point · FDCW241 gateway
Management / cloudCerberus DMS · Cerberus-Remote · Cerberus Mobile · Cerberus Connect X300 · BACnet

Control panels (FC72x)

Cerberus PRO panels share a common operating concept, automatic configuration and networking capability, and differ mainly in loop count, address capacity and expandability. Compact panels (FC721/FC722/FC724) integrate a fixed number of C-NET loops; modular panels (FC723/FC726) add card slots for line cards and I/O cards. Every panel includes an integrated operating unit, integrated power supply and an Ethernet (RJ45) port, and can run standalone or as a network node. The FT724 is a fire terminal — a networked operating/indication node without its own detection loops.

Panels are supplied in Eco, Standard, Comfort and Large housings, with 70 W or 150 W power supplies and batteries from 7 Ah up to 100 Ah (Large), giving up to 72 hours of emergency standby. The integrated operating unit can be augmented with add-ons of 24, 48 or 96 LED display groups for zonal indication, plus optional event printer and Kaba/Nordic key switches. Floor repeater terminals (FT2010/FT2011) provide remote display and control — up to 8 per FC721/FC722, 16 per FC724, 50 per FC726.

Panel family & capacity
PanelC-NET loops (with extension)Max addressesRole / notes
FC7211 (—)126Compact single-loop entry panel
FC7222 / 4 (4 / 8 with extension)252Compact 2-loop panel (US: FC922)
FC7244 / 8 (8 / 16 with extension)504Compact 4-loop panel (US: FC924)
FC7232 base + module slots756Modular; 2 card slots (line / I/O cards)
FC7264 base + 5 module slots1,512Modular; up to 28 loops / 56 stubs; router-capable
FT724— (no loops)Networked fire terminal (operation / indication)
Housings, power & operation
HousingDimensions (W×H×D)Power supplyMax battery
Eco430 × 398 × 80 mm70 W (option on FT724)2×12 V, 7 Ah
Standard430 × 398 × 160 mm70 W or 150 W2×12 V, 26 Ah
Comfort430 × 796 × 160 mm150 W2×12 V, 26 Ah
Large430 × 796 × 260 mm150 W (+ optional 2nd)2×12 V, 45–100 Ah

C-NET detector bus

C-NET is the modern multi-purpose bus that connects detectors, modules, call points and sounders to the panel. It is engineered for rapid, fail-safe communication and flexible installation: it accepts shielded or unshielded cable, requires no shielding, integrates existing star-shaped cable networks without modification, and powers most bus elements directly over the two-wire line (exceptions include certain transponders, LaserFOCUS, the XC10 extinguishing unit and the FDA aspirating detectors, which take a separate supply).

On the modular FC723/FC726, additional detection capacity is added with line cards: the FCL2001 C-NET line card (252 C-NET devices on 4 loops or 8 stubs) and the FCL7201 SynoLOOP card (128 devices per loop / 4 stubs). I/O cards (FCI2007 alarm/fault transmission, FCI2008 twelve programmable I/O, FCI2009 eight monitored horn/output lines) round out the modular slots.

C-NET parameterValue
TopologyLoop, stub (spur) and star; mix supported
Bus elements per loopUp to 252
T-taps per loopUp to 40
Cable lengthUp to 3.3 km with up to 252 elements
CablingShielded or unshielded, twisted or untwisted; no shielding required
PowerBus elements powered over C-NET (with noted exceptions)
IsolationShort-circuit isolators integrated in devices / line isolators
Loop extensionFCI2003 doubles loops while keeping total address count (e.g. 2→4 loops)

Networking — C-WEB cluster & backbone

Cerberus PRO networking has two complementary layers, both with redundant ring wiring. The C-WEB/SAFEDLINK cluster connects up to 32 fire control panels and fire terminals on a two-wire system bus (up to 16 panels when connected to a danger management system). Copper runs reach 1 km between panels (2 km with a repeater); fibre reaches 4 km multi-mode or 40 km single-mode. A second network module enables degrade-mode redundancy even on systems with more than 512 detectors.

The C-WEB/LAN backbone connects clusters over an Ethernet/fibre backbone using industrial LAN technology — Siemens offers this as an EN 54-approved solution. Up to 14 clusters of up to 16 panels each give an EN 54-compliant system of up to 64 panels, with system-wide control, redundant circular wiring and fibre links between clusters. Up to five panels can hold a system-wide view, and any FC726 can act as a router panel — scaling from a single standalone panel to a multi-building campus spanning tens of kilometres on fibre.

ASA detection technology

At the heart of Cerberus PRO detection is ASA — Advanced Signal Analysis. Rather than comparing a single sensor reading against a fixed threshold, ASA continuously analyses the sensor signals with neural, time- and process-dependent algorithms and compares them against stored danger patterns. Each detector can be assigned an application-specific parameter set (a “danger level” profile) tuned to its environment — office, workshop, kitchen, car park, dusty or high-airflow space — so the same hardware can be optimised for maximum sensitivity in clean rooms or maximum deception immunity in harsh areas.

The practical benefits are high early-warning sensitivity to genuine fire signatures combined with strong resistance to unwanted alarms from steam, dust, exhaust and cooking aerosols, plus a high degree of immunity to electrical interference. ASA underpins the multi-sensor OH720 and the neural OOH740 / OOHC740 detectors, and the same philosophy of digital signal analysis extends to the ASD+ aspirating range. Combined with C-NET’s automatic device configuration, ASA also speeds commissioning: detectors are recognised, addressed and given sensible default parameter sets, which the engineer then refines per zone.

Point detectors

The Cerberus PRO FD720 detector range connects directly to C-NET and shares a common low-profile design and detector base. All automatic detectors carry a built-in line isolator option and bicolour status indication.

Detector bases provide the mechanical and electrical interface and add functions: standard base, the DBS720 sounder base (adds an audible signal at the detector), the FDSB226 sounder-beacon base (audible + visual), and relay bases. Sounder bases let designers distribute notification at detector points without separate sounder circuits.

DetectorType / sensorsPrinciple & typical use
OP720Optical smokeScattered-light smoke detection for standard smoke risks
OH720Multi-sensor (optical + heat)Combined smoke + heat with ASA; faster, more robust response
OOH740ASA neural fire detector (optical + heat)Neural multi-criteria sensing; high sensitivity + deception immunity
OOHC740ASA neural fire + CO (optical + heat + CO)Adds carbon-monoxide sensing for smouldering fires & extra immunity
HI720Heat detector (max + rate-of-rise)Where smoke detection is unsuitable; responds to rate of rise
HI722Heat detector (max only)Fixed-temperature heat detection

Special detectors — beam & flame

For spaces where point detectors are impractical, Cerberus PRO offers line and flame detection on the same C-NET loop:

  • FDL241-9 linear (beam) smoke detector — projected-beam detection across large open volumes such as atria, warehouses, halls and heritage spaces, where mounting point detectors across a ceiling is impractical.
  • FDF241-9 flame detector — multi-sensor / triple-IR flame detection for fast-developing flaming fires and high-risk areas (fuel handling, hangars, process areas).
  • Ex / intrinsically-safe variants — the FDCL221-Ex line adapter and Ex-rated devices (e.g. OOH740-A9-Ex, FDM223-Ex) extend detection into hazardous areas on a C-NET-Ex line.

Aspirating smoke detection — ASD range (FDA221 / FDA241)

Aspirating smoke detectors (ASD) actively draw air from the protected area through a network of sampling pipes with calibrated holes, and analyse it in a detection chamber. They suit applications where point detectors are pushed to their limits — high ceilings, cavities and voids (false floors/ceilings), clean rooms, data and telecommunication centres, cable tunnels, conveyor belts, and spaces with strong airflow or electromagnetic fields.

The Siemens ASD detectors FDA221 and FDA241 use patented dual-wavelength technology (blue and infrared light) to detect a wide spectrum of particle sizes and trigger an alarm at the earliest possible moment, with a uniquely dust-resistant detection chamber. They are designed for standalone operation and configured via a USB interface using the ASD Asyst Tool pipe-design software. The FDA241 adds a dust indicator and a chamber cleaning (“blowing out”) function.

ASD specifications
ParameterFDA221FDA241
Monitoring area (per device)Up to 500 m²Up to 800 m²
Max single pipe length30 m60 m
Max branched pipe length2 × 25 m2 × 60 m
Optical principleDual wavelength (blue + infrared)Dual wavelength (blue + infrared)
Alarm parameter sets5 (Fire 1) / 5 (Fire 2)10 (Fire 1) / 10 (Fire 2)
Fire-1 sensitivity range0.20–2.0 %/m obscuration0.05–2.0 %/m obscuration
Relay alarm outputs / fault relay3 / 14 / 1
Dust indicator & cleaningYes (dust indicator + blow-out)
Operating voltage / currentDC 19–30 V; 150 mA (250 mA alarm)DC 19–30 V; 150 mA (250 mA alarm)
Config interfaceUSB + ASD Asyst ToolUSB + ASD Asyst Tool
Pipe / protection25 mm OD pipe; IP3025 mm OD pipe; IP30
ApprovalsEN 54-20 / EN 54-17; VdSEN 54-20 / EN 54-17; VdS

Aspirating smoke detection — ASD+ range (FDA261 / FDA262)

The ASD+ range (FDA261 and FDA262) is Siemens’ digitalised, high-performance aspirating generation, designed for large and demanding protection areas. Its headline capability is coverage: a single ASD+ device can protect an area of up to 6,700 m², dramatically reducing the number of detectors, pipes and commissioning points on large sites. Unlike the standalone ASD detectors, ASD+ units connect directly to the addressed FDnet/C-NET detector line (or can run standalone), so they appear as intelligent, individually addressed devices on the loop alongside point detectors.

ASD+ uses two independent detection chambers and a dual-wavelength signal-processing algorithm that reliably differentiates smoke particles from dust, giving both very high sensitivity (Class A) and maximum immunity to false alarms. Configuration is done over a wireless interface using a mobile app, and pipework is designed with the ASD Asyst Tool. The two models differ mainly in pipe capacity — and therefore the area one device can cover.

ASD+ specifications
ParameterFDA261FDA262
ConnectionFDnet / C-NET addressed line, or standaloneFDnet / C-NET addressed line, or standalone
Max coverage (per device)Up to 6,700 m² (lowest class)Up to 6,700 m² (lowest class)
Class A high-sensitivity coverageUp to ~2,000 m²Up to ~2,000 m²
Total branched pipe lengthUp to 800 mUp to 1,200 m
Detection chambersTwo independent chambersTwo independent chambers
Signal processingDual-wavelength; smoke-vs-dust discriminationDual-wavelength; smoke-vs-dust discrimination
Detection classesClass A / B / C selectableClass A / B / C selectable
ConfigurationWireless interface + mobile app; ASD Asyst ToolWireless interface + mobile app; ASD Asyst Tool
ApprovalsEN 54-20 / EN 54-17; ActivFire (afp-3778)EN 54-20 / EN 54-17; ActivFire (afp-3778)
ASD vs ASD+ — how to choose
AspectASD (FDA221/241)ASD+ (FDA261/262)
IntegrationStandalone (relay outputs to panel)Addressed on FDnet/C-NET loop, or standalone
Coverage / deviceUp to 500 / 800 m²Up to ~6,700 m² (class-dependent)
Pipe lengthUp to 2×25 / 2×60 m branchedUp to 800 / 1,200 m branched
Detection chambersSingle chamberTwo independent chambers
ConfigurationUSB + Asyst ToolWireless app + Asyst Tool
Best forSmall–medium critical rooms, transport, dusty areas (filter box)Large halls, warehouses, multi-zone & high-coverage sites

Input/output modules & isolators

Cerberus PRO interfaces to third-party plant, conventional zones and control functions through C-NET modules. All are loop-connected and most are loop-powered, with built-in short-circuit isolation. On modular panels these are complemented by panel I/O cards: FCI2007 (alarm/fault routing), FCI2008 (12 programmable I/O with defined degrade-mode behaviour) and FCI2009 (8 monitored horn/output lines). Conventional sounder lines can be driven via the FCA2005 sounder module (4 lines).

ModuleFunction
FDCI222Input module — 4 inputs for monitoring potential-free make/break contacts (e.g. sprinkler flow, door, plant status) or alarm actuation
FDCIO222Input/output module — 4 inputs + 4 potential-free relay outputs (AC 250 V / 4 A) for fire-control functions (fans, dampers, AC, lifts)
FDCIO224Input/output module — 4 in / 4 out variant with a different output rating for control applications
Transponders (FDCIO223 / FDCI723)Loop-connected I/O with separate power supply for higher-current or remote control points
Line isolators / FDCL221-ExShort-circuit line isolation; FDCL221-Ex line adapter extends C-NET into intrinsically-safe (Ex) areas
Output module 230 V (FCA1209)Connects directly to a monitored output line; provides a potential-free contact for ventilation, AC, lift control etc.

Manual call points

Cerberus PRO manual call points are C-NET-addressed with an integrated line isolator and built-in alarm LED. The glass-plate / resettable-element design allows the unit to be reset for re-use after activation. Call points are available in red (fire) and other colours for special functions (e.g. manual extinguishing release DM1103-L / emergency-hold DM1103-S in extinguishing systems).

Call pointDescription
FDM221Standard indoor manual call point; direct alarm actuation, integrated line separator, alarm LED
FDM223Manual call point for special / hazardous (Ex) areas
FDM224Manual call point variant (e.g. with additional housing / weather options)
FDM275SWING wireless manual call point (radio, via FDCW241 gateway)

Sounders, beacons & voice-sounders

Audible and visual notification can be delivered from dedicated devices or from detector sounder bases, all on C-NET. Sounder bases and beacon bases let designers distribute notification at detector locations, reducing dedicated sounder circuits; conventional sounder lines remain available via panel sounder outputs and the FCA2005 sounder module, and voice-evacuation is supported through dedicated voice equipment and EVAC modules where required.

DeviceFunction
FDS221C-NET alarm sounder
FDS224-RAlarm sounder (red)
FDS227-RRVoice-sounder beacon — combined voice/tone audible plus visual beacon
DBS720Sounder base — adds an audible signal at the detector position
FDSB226-WRSounder-beacon base — audible plus visual alarm at the detector

Extinguishing control

Cerberus PRO provides integrated extinguishing (suppression release) control, certified to EN 12094-1. The modular FC723 and FC726 panels host extinguishing functionality, and the FC722/FC724 can be combined with extinguishing kits to form a fire-detection-plus-extinguishing panel. Extinguishing outputs support monitored actuation up to ~2 A with line monitoring (ground fault, leakage, open line), and extinguishing key switches (Kaba / Nordic) provide operation clearance.

  • XCA2005 extinguishing control kit (1 sector) — extinguishing card XCI2005, card cage and accessories; monitored valve/standard/inverse outputs and monitored collective inputs (manual release, emergency hold, loss-of-agent, discharged contact).
  • XCM7202 extinguishing terminal & XT2001 remote terminal — operator interface for an extinguishing sector with configurable LEDs/buttons and a countdown display.
  • XC10 extinguishing control unit — C-NET-connected extinguishing controller for room/object protection (single-sector flooding with optional reserve cylinder bank), with manual release (DM1103-L) and emergency-hold (DM1103-S) call points.

Wireless — SWING

For areas where cabling is impractical (heritage buildings, temporary installations, hard-to-reach spaces), Cerberus PRO supports SWING radio devices that participate in the same system as wired C-NET devices. Wireless devices retain ASA detection behaviour and are managed and annunciated identically to wired devices, allowing mixed wired/wireless designs on one system.

SWING deviceFunction
FDCW241SWING radio gateway — links wireless devices to the C-NET loop
FDOOT271SWING radio neural (ASA) fire detector
FDM275SWING radio manual call point

Management, remote access & cloud

Cerberus PRO is managed and integrated through a family of software products that scale from a single panel to enterprise estates. Licence tiers (S1–S4) progressively unlock Cerberus-Remote/BACnet supervision, basic and extended commands, Cerberus Mobile, and activation/deactivation commands — so integration capability is matched to the project. All remote/cloud connectivity is intended to be deployed per Siemens’ network security guidelines (router/firewall/VPN).

ProductRole
Cerberus DMSDanger management station — graphical management and control of fire (and integrated security/building) events across networked panels
Cerberus-RemoteRemote access to a panel/network from a PC (e.g. for diagnostics); enabled per panel via an S1+ licence key
Cerberus MobileMobile app for remote status and notifications (higher-tier licence)
Cerberus Connect X300 (FG2004)Cloud connection gateway linking the system to FS cloud applications and remote services
BACnet integrationThird-party head-end integration via tiered licence keys (S1–S4): supervision, basic, extended and activation/deactivation command levels
Cerberus Engineering ToolPanel configuration / programming software; works with C-NET automatic device configuration
Event printers / repeatersFTO2001 (internal) / DL3750+ (external) printers; FT2010/FT2011 floor repeater terminals

Approvals & standards

Cerberus PRO is certified to the EN 54 fire-detection standards in its home markets and carries regional listings elsewhere:

  • Panels & power — EN 54-2 (control and indicating equipment) and EN 54-4 (power supply), with CPR Declarations of Performance, plus VdS and LPCB approvals.
  • Detectors & devices — EN 54 device parts as applicable: EN 54-17 (isolators), EN 54-18 (I/O devices), EN 54-20 (aspirating detectors); ASD/ASD+ carry CPR DoPs and VdS.
  • Networking — the C-WEB/LAN Ethernet backbone is offered as an EN 54-approved networking solution.
  • Australia / New Zealand — Cerberus PRO panels and devices carry ActivFire listings for the AS 7240 market (for example, the FDA262 ASD+ aspirating detector is ActivFire-listed under afp-3778). Confirm the specific listing for each component and configuration.
  • Extinguishing & transport — extinguishing control to EN 12094-1; the ASD FDA221/241 additionally hold rail approvals (EN 50155, EN 45545-2) and SIL2 (EN 61508).

Applications & summary

The breadth of the Cerberus PRO range lets a single platform protect a wide spectrum of buildings: offices and retail, hotels and residential, education and health campuses, industrial and process facilities, data and telecommunication centres, transport (including rail/rolling-stock with the ASD range), car parks, warehouses and atria (beam and ASD+), and hazardous areas (Ex devices). Standalone panels suit small buildings; SAFEDLINK clusters and the LAN/fibre backbone scale to multi-building estates.

Its defining strengths are ASA neural detection for sensitivity with false-alarm immunity; the flexible, fail-safe C-NET bus with automatic configuration; an exceptionally deep aspirating offering spanning the compact ASD range and the high-coverage ASD+ range (up to 6,700 m² per device); modular extinguishing control; and a mature management/cloud ecosystem (Cerberus DMS, Remote, Mobile, Connect X300, BACnet). Together these make Cerberus PRO a complete, scalable life-safety platform rather than a single panel — engineered to grow from one loop to a kilometres-wide, multi-building network on a common toolset.

Siemens solution partners in Australia

Cerberus PRO is supplied and supported through Siemens’ accredited solution partners. Australian distributors include:

Partner coverage and accreditation can change — confirm current details with the distributor or Siemens.

Further reading

Siemens fire safety (official) Cerberus PRO panels & network brochure (BT_0149) ASD+ FDA262 ActivFire certificate (afp-3778) Why an asset register matters

Frequently asked

Who makes Cerberus PRO?

Cerberus PRO is a fire detection line made by Siemens, within its Siemens Smart Infrastructure division. The Cerberus brand has Swiss origins — Cerberus AG — which Siemens acquired in 1998.

What is ASAtechnology?

ASA (Advanced Signal Analysis) is Siemens’ multi-criteria detection technology. Its detectors combine multiple sensing elements with signal processing to distinguish real fires from nuisance sources, which helps reduce false alarms in challenging environments.

How is Siemens Cerberus PRO sold in Australia?

It uses an engineered-systems model. In Australia, Cerberus PRO is engineered, supplied and supported through Siemens and accredited solution partners rather than sold off the shelf, so programming and spares flow through those partners.

Compare with other brands
Notifier (Honeywell) Ampac Pertronic
All fire protection systems brands