Addressable optical-plus-heat detector that combines smoke with rate-of-rise, aimed at hotel bedrooms and other nuisance-prone spaces.
The detector runs two independent signals into an onboard microcontroller: an optical signal representing the smoke level near the head, and a temperature signal representing the air temperature near it.
The important part is what happens to the temperature signal. The processing extracts only rate-of-rise information to combine with the optical signal, which means the detector will not respond to a slow temperature increase even if the temperature eventually reaches a high level. It is watching the rate of change, not absolute heat. A large, sudden temperature change can produce an alarm on its own, without smoke, if it is sustained for 20 seconds.
That optical-plus-rate-of-rise combination is what gives the XP95 MultiSensor its broad fire sensitivity while resisting nuisance triggers — and it is also why it should not be treated as a substitute for a heat detector in a position that needs one.
| Specification | Rating |
|---|---|
| Operating voltage | 17 to 28 VDC |
| Quiescent current | 500 µA average |
| Alarm current (LED on) | 3.5 mA |
| Remote LED current | 4 mA at 5 V |
| Dimensions | 100 mm dia × 58 mm H (including base) |
| Operating temperature | −40 °C to +70 °C (no icing) |
| Relative humidity | 0 to 95% non-condensing |
| IP rating | 23D (indoor use) |
| Weight | 160 g (including base) |
| Approval scheme | Item number | Description |
|---|---|---|
| LPCB (CEA 4021) | 55000-885AMP | XP95 MultiSensor Detector |
| SAI Global (AS 7240.15) | 4106-2004 | XP95 MultiSensor Detector |
Figures on this page are the manufacturer’s published specifications, taken from Ampac product data sheet PDS4106-2004-1. They are reproduced for reference and are not installation, design or compliance guidance. Work from the current Ampac datasheet, Product Guide MAN3037 and host-panel compatibility documentation, and design to the applicable edition of AS 7240 and local codes.
No. The thermal path uses rate-of-rise only, so a slow temperature increase will not trigger it even if the temperature eventually reaches a high level. Smoke is the primary path; heat contributes through rate of change.
Yes, but only on a large, sudden temperature change sustained for 20 seconds — not on gradual heating.
The datasheet states it may be used in place of an ionisation detector in many instances. Confirm suitability for the specific application and standard rather than treating it as a blanket substitution.
It depends on the approval scheme: 55000-885AMP for LPCB / CEA 4021, or 4106-2004 for SAI Global / AS 7240.15.
No — the datasheet lists it as unaffected by wind or atmospheric pressure.
No. It is IP 23D, indoor use, with an operating range of −40 °C to +70 °C and no icing.