HOME/KNOWLEDGE BASE/EWIS SYSTEMS/AMPAC EVACU^ELITE
EWIS Systems

AMPAC EvacU^Elite

Scalable EWCIE with fully integrated warden intercom, 512 zones and 1024 handsets across a 64-node fault-tolerant network.

EWCIEIntegrated EICIELoop intercomNetworked evacuation
OriginAustralia (Perth, WA)
OwnershipHalma plc (UK)

Cabinets and user interface

Two cabinet sizes cover the range: a 13U wall-mount and a 24U floor-standing. Each supports universal rack frame assemblies, touchscreen GUIs, power supplies and module cards.

The primary GUI is a 9-inch touchscreen carrying the menu system plus common and individual controls and indicators for emergency zones. Secondary GUIs add further zone controls as required — up to 4 on the 13U and 8 on the 24U.

Modules

  • Distribution CPU card / network interface card — system processing and networking
  • 8-way output card for strobes and VADs, with an optional 2-wire reverse-polarity connection
  • 8-input multi-purpose interface card with high-level interface
  • Dual 25 W amplifier; single output 50 W amplifier; 150 W amplifier with built-in 4-way splitter
  • 4-way radial warden handset interface (ILC) for point-to-point phones
  • Dual loop warden handset interface (LILC) — 20 handsets per loop, 40 WIPs per card
  • Public address interface card (PAIC), including the Bosch Praesensa high-level interface

Intercom and audio

The intercom supports two interface types to the warden handsets. Radial, point-to-point wiring runs a single pair to each handset, each with a remote buzzer output for handsets inside a security enclosure. The fault-tolerant loop wires handsets in a loop to save install time and cable, on a two-wire design with a short-circuit isolator at every handset. Each handset also has a connection for an emergency alarm initiating device.

Audio is digital throughout, including across the network. Alert and evacuation tones are generated in software while pre-recorded messages are stored as audio files and distributed per the programmed configuration. Audio mapping software routes any source or file to any amplifier, which is what allows multiple alert and evacuation messages to run as part of a phased sequence. Background music inputs are supported for non-emergency use.

Capacity and specifications

System capacity
ItemSpecification
Max emergency zones512
Max warden handsets (WIPs)1024
Max nodes64
Graphical user interfaces13U — 4; 24U — 8
Universal rack frames13U — 2; 24U — 5
Universal rack frame
ItemSpecification
Slots16, plus a dedicated slot for the CPU
Max dual 25 W / 50 W / 150 W amplifier cards8 each
Max EIS line cards (radial or loop)16
Max multi-purpose interface cards16
Max multi-purpose output cards6
Max PAIC1
Max current per rack48 A
Cabinets, power and environment
ItemSpecification
Cabinet options13U wall-mount and 24U floor-standing
Dimensions (13U)H 900 × W 650 × D 380 mm
Dimensions (24U)H 1800 × W 650 × D 380 mm
Power supply (max)13U — 2.4 kW; 24U — 3.6 kW
Max battery size (pair)13U — 100 Ah; 24U — 190 Ah
Mains current (max)13U — 13 A; 24U — 19.5 A (25 A breaker)
External operating voltage204–264 V AC
Temperature / humidity−5 °C to +50 °C; 0–95% non-condensing
Warning device outputs and networking media
ItemSpecification
Visual warning device outputContacts rated 2 A; max current draw 6 A
2-wire single-end outputs8 × 750 mA
Reverse-polarity option4 outputs × 1.5 A each
2-core copper0.75 mm² twisted and screened (Flex DSL SFP)
Cat 5/6eUp to 100 m
FibreSingle-mode and multi-mode; highest bandwidth over fibre
Graphical user interface
ItemSpecification
Display9" TFT LCD, 800 × 480, LED backlight, resistive touchscreen
Microphone600 Ω with capsule monitoring
Emergency intercom handsetElectret capsule with 150 Ω speaker
USB / SDHost (USB stick) and device (mini USB); SD card supported
HLI to FDCIE1 × RJ45, RS485 signal levels using 6350-MIC
Ethernet2 × RJ45, proprietary power and transformer isolation
Inputs2 monitored and 2 unmonitored
Current consumption0.185 A quiescent; 0.207 A active

Figures on this page are the manufacturer’s published specifications, taken from Ampac datasheet PDS6350-0001-11. They are reproduced for reference and are not design, compliance or engineering advice. Confirm every figure against the current datasheet and installation manual, and design to the edition of the standard that applies in your jurisdiction.

Further reading

Compare it with the VIGILANT QE20 Ampac brand deep-dive EWIS testing under AS 1851

Frequently asked

How big can an EvacU^Elite system get?

The software supports up to 512 emergency zones and 1024 warden handsets, across up to 64 nodes in a fault-tolerant loop network. A 24U cabinet takes 5 universal rack frames and 8 GUIs; a 13U wall-mount takes 2 rack frames and 4 GUIs.

What is the advantage of the loop intercom?

Handsets are wired in a loop rather than point-to-point, which saves install time and cable. The design is two-wire, against four-wire configurations elsewhere in the market, and every handset carries a short-circuit isolator so the rest of the loop keeps working through a short. If the loop is broken the system identifies which two WIP addresses the break sits between.

Does it work with non-Ampac fire panels?

Yes. There is a high-level interface to the Ampac FireFinder^PLUS, and third-party fire detection systems connect through low-level hardwired inputs. A Bosch Praesensa high-level interface is supported via the public address interface card.

Can evacuation sequences be tested before commissioning?

The PC configuration tool includes a sequence builder and an integrated simulator, so sequences can be configured and tested before site commissioning, then sent to a single panel over USB or across the network.

Compare with other brands
VIGILANT QE20
All ewis systems brands

Run your whole trades business in one place