HOME/BLOG/FIRE PROTECTION
Fire protection

Fire pumpset testing under AS 1851: electric vs diesel, run tests and flow tests

11 September 2026 · 14 MIN READ
Fire pumpset testing under AS 1851: electric vs diesel, run tests and flow tests

When a hydrant or sprinkler system needs more pressure or flow than the town main can give, a fire pumpset makes up the difference. It sits in a plant room for years doing nothing, and then it has to start first time, run without supervision and deliver its design performance for as long as the fire brigade needs it. Routine servicing is the only way anyone knows whether it will.

Fire pumpsets have their own section in AS 1851-2012 (Section 3), and they carry some of the most important readings in the whole standard. Their flow and pressure performance is one of the few areas where AS 1851 requires baseline data. A pump left in manual, a closed valve or a flat battery bank can quietly disable the system it serves.

This guide explains how electric and diesel pumpsets differ, the service frequencies and tolerances, how to run a monthly start test, how annual flow testing works, where pressure maintenance pumps fit in, which findings are critical defects, and what to record.

What a fire pumpset is

A fire pumpset is more than a pump. Pumpsets are designed and installed to AS 2941, and the “set” is the whole assembly that has to work together:

Pumpsets serve hydrant systems, sprinkler systems and combined systems, drawing from the town main, storage tanks or both. Knowing what the pump serves, and where its water comes from, matters as much as the pump itself.

Electric vs diesel pumpsets

Many buildings have one of each: an electric pump as the duty pump and a diesel as the standby, so the system still works if the power fails. They need the same outcome from servicing (start automatically, run reliably, deliver the duty point), but they fail in different ways, so the checks differ.

Electric pumpsetDiesel pumpset
Energy sourceThe building’s electrical supply, through a dedicated fire-rated supply to the controllerA diesel engine with its own fuel supply, independent of mains power
StartingThe controller starts the motor on a drop in system pressureThe controller cranks the engine from its batteries on a drop in system pressure; diesel pumpsets are fitted with duplicated batteries and chargers so one failure doesn’t stop the start
StoppingOnce started automatically, it keeps running until someone stops it manuallyOnce started automatically, it keeps running until someone stops it manually at the pumpset
What usually goes wrongSupply isolated or tripped, controller left in manual or off, phase failure, motor or bearing wearFlat or failed batteries, charger faults, fuel low or degraded, cooling water or coolant problems, leaks, controller left in manual or off
Extra things to checkSupply available at the controller, isolator secured on, phase and supply indicationsFuel level and condition, both battery banks and both chargers, lubricating oil and coolant, cooling water discharge, belts, hoses, exhaust and leaks
Why fire pumps don’t stop themselves
A fire pump is designed to keep running once it has started automatically. The controller doesn’t shut it down when pressure recovers. That’s deliberate: a pump that stops itself in a fire is worse than one that runs too long. It means every automatic start test ends with somebody stopping the pump by hand and returning the controller to automatic.

Frequencies and tolerances

AS 1851-2012 sets out the routine service activities for fire pumpsets in Section 3, at the intervals below. The tolerances (how far either side of the scheduled date the activity can be carried out) come from Table 1.11(B), as summarised in Building Commission NSW’s good practice guide:

IntervalToleranceNotes
Monthly± 5 working daysThe routine start and run test
Six-monthly± 1 month
Yearly± 2 monthsIncludes the annual performance (flow) test
Two-yearly± 2 monthsReplace diesel engine start batteries irrespective of condition, and record the date on the battery and in the site records (Table 3.4.3, item 3.5)
Five-yearly± 3 monthsRepack pump glands; overhaul circulation-relief, pressure-relief, engine cooling and pressure-regulating valves; repack stop valves; check ball and butterfly valves are holding (Table 3.4.4)

The exact activities for each interval are in the Section 3 tables of the standard, and each is recorded as a pass or fail in the logbook against its section and interval. A service carried out outside its tolerance is an out of tolerance activity: it’s recorded in the logbook as a non-conformance, and the service is carried out as soon as practical.

The standard itself is the reference. Buy a current copy, check which amendments you’re working to, and make sure your task sheets list the activities the Section 3 tables actually require, not what the last contractor’s checklist happened to include.

The monthly start test

The monthly test proves the most important thing a fire pump does: start by itself when system pressure drops. Starting the pump with a button proves the motor or engine works. It doesn’t prove the pressure switch, the controller and the start circuit will work in a fire.

Before you start

Running the test

  1. Simulate demand by lowering pressure at the pressure switch (typically by opening its test or drain valve) so the controller starts the pump on falling pressure, just as it would in a fire.
  2. Record the pressure at which the pump started: the cut-in pressure.
  3. For a diesel, confirm the engine can start from each battery bank.
  4. Let the pump run for the period the standard and the manufacturer specify, long enough for pressures and temperatures to settle.
  5. While it runs, record suction and discharge pressure, speed, and for a diesel the engine temperature, oil pressure and charging.
  6. Look and listen: unusual noise or vibration, overheating, leaks, gland leakage outside the normal range (packed glands are meant to drip), and cooling water discharging where it should.
  7. Check the circulation relief is discharging so the pump isn’t overheating against a closed system.
  8. Stop the pump manually, then return the controller to automatic.

Before you leave

Annual performance and flow testing

The monthly test proves the pump starts and runs. The annual test proves it still delivers: the flow and pressure the system was designed to rely on. This is where baseline data matters.

Under clause 1.8 of AS 1851-2012, baseline data is limited to what the approved design required and what’s needed to verify a routine service result. Building Commission NSW’s guide says the only routine service activities it applies to are the flow and pressure performance data for sprinkler systems, hydrant systems, fire pumpsets and some mechanical service features. For a pumpset, that performance benchmark usually comes from:

What to measure

Plot the results against the performance curve and last year’s results. A pump that produces less pressure at the same flow than it used to is telling you something: worn impeller or wear rings, a partially closed valve, a blockage, or a speed problem. A falling suction pressure points back to the water supply.

Where the baseline data isn’t available, AS 1851-2012 is clear: carry out the test, record and report the result, and record and report the missing baseline data as a non-conformance. Don’t adopt this year’s result as the new baseline, because a reading from a worn pump would lock in the wear.

Flow testing discharges a lot of water. Plan where it goes, whether it can be recirculated to a tank, who needs to be told, and whether the water authority or site has any conditions. Do this before the day, not on it.

Planning the annual test

Pressure maintenance pumps

The pressure maintenance pump keeps the system topped up so that small losses (a weeping valve, a minor leak, temperature changes) don’t start the main pump. It starts at a higher pressure than the main pump, so it acts first.

Critical defects in the pump room

A critical defect is one that has rendered the system inoperable and is reasonably likely to have a significant adverse impact on the safety of occupants in a fire. Because a pumpset is often the only way a hydrant or sprinkler system can reach its design performance, a pumpset failure frequently meets that test. Findings that commonly do:

A critical defect must be reported to the building owner or their nominated representative before you leave site, or as soon as possible, and confirmed in writing within 24 hours. Lower-order issues, such as a gauge that needs replacing or a missing label, are generally non-critical defects or non-conformances, notified within one week. Classify on the evidence, and record why.

Case study: a pumpset replacement that needed approval
Building Commission NSW’s good practice guide describes a five-storey residential building whose hydrant pumpset failed catastrophically during its annual load test. The contractor quoted a replacement built to the same Australian Standard; the building’s accredited practitioner advised the owners to contact council urgently, and council issued a Fire Order covering the replacement. After commissioning, an independently witnessed water supply proving test was carried out and the owners received a certificate of compliance. There was no change to the fire safety schedule, but the works still needed council approval. The lesson: a like-for-like pumpset replacement isn’t automatically “just a repair”.

What to record

ReadingWhy it matters
Standing system pressureThe starting point for the test, and a check on the pressure maintenance pump
Cut-in pressureProves the automatic start works at the right pressure
Suction and discharge pressure while runningSeparates pump performance from water supply performance
Churn (no-flow) pressureA quick annual indicator of pump condition
Flow and pressure at the duty pointThe core evidence the pump still meets its design
SpeedPerformance depends on it; a slow driver means low output
Diesel engine readingsTemperature, oil pressure, charging, fuel level and battery condition
Jockey pump start and stop pressuresCorrect sequencing, and early warning of leaks
Controller mode on departureProof the pump was left in automatic

Keep the readings against the pumpset itself, year after year. A single test result is a pass or fail; five years of results side by side show a pump wearing out before it fails.

Taking over a pump room

On the first visit to a new site, spend a few extra minutes building the pumpset’s record:

Working safely

Common mistakes

How traqR helps
Technicians in traqR run the Pump Flow Test from the iPhone app, capturing readings against the pumpset on the site’s asset register, and it works offline in plant rooms with no signal. Recurring schedules keep monthly, six-monthly and yearly services inside their AS 1851 tolerances. If a technician records a critical defect (a pump left in manual, a closed valve, a failed start), traqR alerts admins and the site contact straight away, and the tech can’t sign off until they’ve recorded telling the site.

Frequently asked questions

How often do fire pumps need to be tested under AS 1851?

AS 1851-2012 sets monthly, six-monthly, yearly, two-yearly and five-yearly routine service activities for fire pumpsets. The monthly tolerance is five working days either side of the scheduled date.

Should the monthly test start the pump automatically?

Yes. Lowering pressure at the pressure switch so the controller starts the pump proves the whole start circuit works. A manual start only proves the driver runs.

Why doesn’t the fire pump stop when pressure is restored?

Fire pumps are designed to keep running once started automatically, so they can’t shut themselves down during a fire. They’re stopped manually.

What if there’s no pump curve or commissioning data?

Carry out the test and record the results, and record and report the missing baseline data as a non-conformance. The data plate, the manufacturer and the original installer are the first places to look for the curve.

Is a pump left in manual a critical defect?

Usually. If the pump can’t start automatically when the system needs it, the system it serves may not perform in a fire. Tell the responsible entity before you leave and confirm it in writing within 24 hours.

Does replacing a fire pumpset need approval?

It can. In Building Commission NSW’s case study, a like-for-like replacement still required council approval. Check before committing to the work.

Sources and further reading

This article is general information, not engineering advice. Fire pumpset servicing must follow the current edition of AS 1851, the pumpset manufacturer’s instructions and the system’s approved design, and be carried out by competent, appropriately licensed people.
Keep reading
Baseline data in AS 1851, and what to do when it’s missing Critical defects under AS 1851: reporting rules and timeframes Annual fire system testing: the complete AS 1851 guide The hidden cost of missed service dates Fire hydrant and hose reel servicing under AS 1851 Backflow prevention on fire services

Run your trade business in one place

Quotes, invoices, scheduling and compliance. Try traqR free for 14 days, no credit card required.

Start free trial View pricing