Fire protection

Fire equipment testing schedule

Pick the fire equipment on site and generate a reference schedule of the AS 1851 routine service activities and how often each is due.

Equipment on site
Tick the fire equipment you want in the schedule.
Fire Equipment Testing Schedule
Indicative AS 1851 routine service frequencies

Routine service activities

EquipmentActivityFrequency
Portable fire extinguishersRoutine inspection & service6-monthly
Pressure test / overhaul5-yearly
Fire hose reelsRoutine service6-monthly
Flow & operation testYearly
Fire blanketsRoutine inspection6-monthly
Fire hydrant systemRoutine service6-monthly
Flow & pressure testYearly
Automatic sprinkler systemRoutine check (alarms, valves, gauges)Monthly
Full serviceYearly
Fire detection & alarm (AS 1670)Routine checkMonthly
Detector & system serviceYearly
Emergency warning & intercom (EWIS)Routine checkMonthly
Full serviceYearly
Emergency & exit lighting (AS 2293)Discharge (duration) test6-monthly
Fire & smoke doorsInspectionYearly
Fire pumpsetRoutine run & checkMonthly
Full serviceYearly

Indicative frequencies only — the exact activities and intervals are set by AS 1851 for each measure and building.

How it works

1

Pick your equipment

Tick the fire protection equipment installed at the site to build a tailored reference schedule.

2

See the frequencies

The schedule lists the routine service activities and their typical AS 1851 intervals — monthly, six-monthly, yearly and five-yearly.

3

Print for the site file

Print or save the schedule as a quick reference for the building’s fire maintenance records.

Frequently asked questions

How often should fire equipment be tested?

It depends on the equipment. Under AS 1851, sprinkler and detection systems have monthly checks and annual services, portable extinguishers are serviced six-monthly with a five-yearly pressure test, hose reels six-monthly and yearly, and emergency lighting has a six-monthly discharge test. This schedule summarises the common intervals.

What does “routine service” involve?

Routine servicing covers inspecting, testing and maintaining the equipment so it will work in a fire — checking gauges and valves, operating and testing systems, replacing consumables, and recording results. The specific tasks for each measure and interval are set out in AS 1851.

Do I have to keep records?

Yes. AS 1851 requires records of routine servicing, and building owners generally must keep evidence that essential fire safety measures have been maintained. These records support periodic fire safety statements where required.

Is this schedule compliant?

It’s an indicative reference to help you plan. The definitive activities and frequencies are in AS 1851 and depend on the measure and building. Servicing must be done and recorded by competent technicians.

This schedule uses indicative AS 1851 frequencies and is a general reference, not a compliance document. The exact routine service activities, intervals and records are set by AS 1851 for each measure and building and must be carried out by competent technicians.