HOME/FREE TOOLS/CABLE SIZE
Electrical

Cable size calculator

Get a starting point for cable sizing: the smallest standard conductor that keeps voltage drop within limits for your load and run — then confirm current-carrying capacity to the standards.

The load & run
What the cable carries and how far it runs.
Minimum cable size (volt-drop)
4 mm²
Smallest standard conductor that keeps drop within 5% for 25 A over 40 m. Actual drop ≈ 4.89%.
Calculated minimum CSA3.91 mm²
Next standard size4 mm²
Voltage drop at that size11.25 V (4.89%)

This sizes for voltage drop only. You must also confirm the cable’s current-carrying capacity for your installation method, grouping and ambient temperature using AS/NZS 3008 — that may require a larger size.

traqR keeps the quote, job and compliance paperwork for each electrical job together — so what you spec on site is what ends up on the invoice.

Start free trial

How it works

1

Set the voltage-drop budget

Your allowable drop (usually 5%) times the supply voltage gives the maximum volts you can lose across the run.

2

Solve for conductor size

Rearranging the voltage-drop formula gives the minimum cross-sectional area that keeps the run within that budget, then we round up to the next standard size.

3

Then check ampacity

Voltage drop is only half the job. The cable must also carry the load current safely under its installation conditions — always confirm against AS/NZS 3008.

Frequently asked questions

How do I choose the right cable size?

Cable selection has to satisfy several things at once: current-carrying capacity for the installation conditions, voltage drop within limits, protection against fault currents, and earth loop impedance. This tool covers the voltage-drop part and suggests the smallest standard conductor that passes it — but the final size is the largest required by any of those checks.

Does this account for current-carrying capacity?

No — it sizes for voltage drop only. The current a cable can safely carry depends on its insulation, how it’s installed (in conduit, buried, on a tray), how many cables are grouped together and the ambient temperature. Those are covered by the derating tables in AS/NZS 3008 and can call for a larger cable than voltage drop alone.

What are the standard cable sizes?

Common conductor sizes step through 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 mm² and up. This tool rounds the calculated minimum up to the next size in that series, since you can’t buy an arbitrary cross-section.

Can I rely on this for compliance?

No. It’s an indicative starting point. Compliant cable sizing must be designed and verified by a licensed electrician against AS/NZS 3000 and AS/NZS 3008, accounting for all the factors above and your specific installation.

This calculator is an indicative aid that sizes for voltage drop only, using approximate resistivity values. It does not determine current-carrying capacity, fault protection or earthing requirements. Cable selection must be designed and verified by a licensed electrician to AS/NZS 3000 and AS/NZS 3008.